XD2000-39P2-4B1221 — 15kW(HD)/18.5kW(ND) Three-Phase Variable Frequency Drive (415V)
The Lauritz Knudsen xD2000 XD2000-39P2-4B1221 is a 15kW/18.5kW 415V VFD built for fan, pump, compressor, and other non-regenerative process applications on a 380–460VAC (-15/+10%), 3-phase, 50/60Hz supply. It combines a compact Frame 3 footprint with an inbuilt EMC filter, galvanic isolation, and (from 4kW ND onward) a built-in DC reactor for reduced harmonics and longer motor cable runs. Explore the complete range in our Lauritz Knudsen variable frequency drives collection.

15kW/18.5kW 415V VFD – Control & Motor Compatibility
The xD2000 supports V/F control (5-point), Slip Compensation, quadratic V/F energy-saving, and Open Loop control of Permanent Magnet synchronous motors. Overload capacity is 150% of rated current for Heavy Duty use and 110% for Normal Duty use, and the output frequency range spans 0.5–500Hz. This 15kW/18.5kW 415V VFD is a strong fit for fans, pumps, compressors, and general utility process applications that do not require regenerative braking.

15kW/18.5kW 415V VFD – Pump & Fan-Specific Features
Built-in PID control (AHU, fan, pump, compressor) supports 4 preset PID references, PID wake-up/sleep with Sleep Boost, and predictive speed (pre-PID frequency). Pump & compressor specific logic adds lead (master) and auxiliary pump selection with fixed and variable speed, FIFO/FILO staging, and booster-pump control with staging and destaging. Stall prevention (deceleration ramp adaptation and current limiting), skip frequency, catch-on-the-fly (flying start), and DC braking during stopping round out the application toolkit.
15kW/18.5kW 415V VFD – Built-in Modbus & Optional Profibus DP
A front-face RJ45 port gives native 2-wire RS485 Modbus RTU connectivity (4800–38400 bps), so the XD2000-39P2-4B1221 links directly to a PLC, HMI, or SCADA system. An optional Profibus DP card (9-pin Sub-D, 9.6–12000 kbps with automatic baud-rate detection) adds native drive profile support (CiA®402) and PROFIdrive, with quick setup from the drive side and support for two masters (MS0/MS1). Detachable, IP21-rated basic LCD keypads (4-line, white backlight, 6 languages, store/download configurations) are standard, with an advanced graphical LCD keypad available as an option.

15kW/18.5kW 415V VFD – Applications
This 15kW/18.5kW 415V VFD is widely used for HVAC fans and AHUs, water and booster pumps, compressors, and other non-regenerative utility and process applications across buildings, water treatment, and light industry. Its enclosure is IP20 (IP4X on top with the vent cover), and the inbuilt EMC filter complies with IEC/EN 61800-3 Category C3 in Environment 1 or 2 for CE marking, with a maximum shielded cable length of 50m.
Technical Specifications
| Model | XD2000-39P2-4B1221 |
|---|---|
| Output Power | 15 kW (Heavy Duty) / 18.5 kW (Normal Duty) |
| Output Current | 31.7 A (HD) / 39.2 A (ND) |
| Supply Voltage | 380–460VAC (-15/+10%), 3-phase, 50/60Hz |
| Frame Size | Frame 3 (S3) |
| Dimensions (W×H×D) | 211 × 495 × 232 mm |
| Weight | 13.5 kg |
| Enclosure | IP20 (IP4X on top with vent cover) |
| Output Frequency | 0.5 – 500 Hz |
| Control Modes | V/F, V/F 5-point, Slip Compensation, V/F Energy Saving & Quadratic V/F, Open Loop Synchronous (PM) Motor Control |
| Overload Capacity | 150% (Heavy Duty) / 110% (Normal Duty) of rated current for 1 min |
| Efficiency at Full Load | 96.6 – 98.3% |
| Communication | Built-in Modbus RTU via RJ45 (2-wire RS485); optional Profibus DP |
| Operating Temperature | -15 to +45°C (without derating), up to +60°C with derating |
| DC Reactor | 0.357 mH – 45A (built-in) |
| Recommended MPCB | MOG-H2M 50A |
| Recommended MCCB | DZ1-160N 50A |
| Recommended Main Contactor | MO 50 / MNX 50 (50A) |
| Cable Sizing (Supply & Output) | 10 (8) mm² (AWG) |
| Standards | CE, RoHS, IEC 61800-3, IEC 61800-5-1, IEC 60721-3 |
Why Buy From Stockhai?
Stockhai supplies authentic Lauritz Knudsen xD2000 drives with fast dispatch and technical support across India. Our team can help you size the right breaker, contactor, and choke for your installation. Browse the full Lauritz Knudsen product range on Stockhai.

Frequently Asked Questions
Does the XD2000-39P2-4B1221 need braking capability? No — the xD2000 series is designed for non-regenerative fan, pump, and compressor applications that do not require dynamic braking.
Can it control Permanent Magnet (PM) motors? Yes, the xD2000 supports Open Loop control of Permanent Magnet synchronous motors in addition to standard induction motors.
Does it come with a DC reactor? Yes, a DC reactor is built in from 4kW(ND) ratings onward, reducing harmonics by roughly 40% at rated load.
Summary
In summary, the XD2000-39P2-4B1221 15kW/18.5kW 415V VFD pairs a Frame 3 footprint with inbuilt EMC filtering, PID-based pump/fan control, and native Modbus connectivity. It is a strong choice for HVAC, water, and general utility process applications, and it ships fast from Stockhai’s warehouse in India.